Thermal battery for heat pump optimization#

EMHASS supports modeling thermal batteries for heat pump systems with thermal mass storage. This is useful when you have a heat pump with underfloor heating or a radiator system with a thermal storage medium like a concrete slab or water-based thermal mass.

The thermal battery model allows you to optimize heat pump operation by taking advantage of:

  • Variable electricity pricing (run the heat pump during cheap periods)

  • Solar PV production (use excess solar energy for heating)

  • Building thermal inertia (pre-heat during low-cost periods)

  • Heat pump efficiency variations with outdoor temperature

This implementation is based on the methodology from Langer & Volling (2020) ā€œAn optimal home energy management system for modular battery electric vehicles (MBEV) and the power gridā€.

The thermal battery model#

A thermal battery stores heat energy in a thermal mass (concrete slab, screed, water, etc.) which can be heated by a heat pump during periods of low electricity cost or high solar production. The stored heat is then gradually released to maintain comfortable indoor temperatures.

The model calculates the evolution of the thermal storage temperature based on:

  • Heat pump operation (with COP depending on outdoor temperature)

  • Heating demand from the building

  • Thermal losses from the storage

The optimizer then determines when to run the heat pump to minimize costs while maintaining the storage temperature within acceptable bounds.

Configuration parameters#

To use a thermal battery, you need to configure it within the def_load_config list. The thermal battery is defined using the thermal_battery key.

Required core parameters#

These parameters define the basic thermal battery system:

  • supply_temperature: The heat pump supply/flow temperature in °C. This is the temperature of water/fluid leaving the heat pump.

    • Underfloor heating: typically 30-40°C

    • Radiator systems: typically 50-70°C

    • Lower temperatures = better heat pump efficiency

    • Example: 35.0 for underfloor heating

  • volume: Volume of the thermal storage medium in m³.

    • For underfloor heating: concrete slab volume (floor area Ɨ screed thickness)

    • For buffer tanks: tank volume in m³

    • Example: 20.0 for a 100m² floor with 20cm screed (100 Ɨ 0.2 = 20 m³)

  • start_temperature: Initial temperature of the thermal storage in °C at the start of optimization.

    • Should match the current actual temperature

    • For underfloor: measure floor surface temperature

    • Example: 22.0

  • min_temperatures: Minimum allowed storage temperatures in °C per timestep (list).

    • Lower bound of the comfort range for each optimization timestep

    • Temperature should not drop below these values

    • Can be constant or vary by time of day (e.g., lower at night)

    • Example: [20.0] * 48 for constant 20°C comfort over 48 timesteps

    • Example: [18.0]*16 + [20.0]*16 + [18.0]*16 for night setback

  • max_temperatures: Maximum allowed storage temperatures in °C per timestep (list).

    • Upper bound of the comfort range for each optimization timestep

    • Safety limit for the storage medium

    • Can be constant or vary by time of day

    • Example: [28.0] * 48 for underfloor heating (avoid too hot floors)

    • Example: [26.0]*24 + [28.0]*24 for different day/night limits

Optional efficiency parameter#

  • carnot_efficiency: Real-world heat pump efficiency as a fraction of the ideal Carnot cycle (default: 0.4).

    • Typical range: 0.35-0.50 (35-50% of ideal Carnot efficiency)

    • Modern inverter heat pumps: 0.40-0.50

    • Standard on/off heat pumps: 0.35-0.42

    • Example: 0.42

    • See the calibration section below for how to determine this

Surface solar gain (pool, outdoor tank, solar-thermal)#

When the thermal mass is directly exposed to sunlight - a pool, an uncovered outdoor buffer tank, or a thermal store fed by a flat-plate solar-thermal panel - the surface absorbs solar radiation and reduces the heating demand seen by the pump or boiler. EMHASS models this absorption as a negative term on the residual heating demand. Set two optional thermal_battery fields to enable it:

  • solar_absorption_area: Effective horizontal absorption surface in m². Defaults to unset (no solar gain term). Set this to the pool surface area, the exposed top of an outdoor tank, or the solar-thermal collector aperture.

    • Example pool: 32.0 for a 4Ɨ8 m pool

  • solar_absorption_factor: Fraction of global horizontal irradiance (GHI) absorbed by the thermal mass (default: 0.7).

    • Uncovered pool: 0.7-0.9 (water absorbs IR strongly)

    • Covered pool / solar cover: 0.2-0.4

    • Insulated tank cover: 0.0-0.1

    • Flat-plate selective absorber: 0.85-0.95

EMHASS reuses the GHI forecast already fetched for PV - no second weather API call. The per-timestep gain is ghi[t] * area * factor / 1000 * dt_hours (kWh) and is subtracted from the heating demand before the optimizer dispatches the heat source.

Seasonal toggle: to stop heating the pool entirely (winter shutdown), either set the pool deferrable load’s nominal_power_of_deferrable_loads[k] to 0 in optim_conf, or omit the load from def_load_config for the off-season config snapshot. The solar-gain term has no effect when the pool load is inactive.

Heating curve mode (weather-compensated heat pump)#

Real heat pumps modulate their supply temperature in response to outdoor temperature, the way modern boiler/HP controllers do. Lower supply temperature when it’s mild outside yields better COP. To enable this behavior in optimization, set heating_curve instead of (or alongside) supply_temperature:

  • heating_curve: Dict describing a linear weather-compensation law: T_supply = clip(offset - slope * T_outdoor, min_supply, max_supply). When present, this takes precedence over the constant supply_temperature field.

    • slope: Kelvin of supply-T change per Kelvin of outdoor-T change. Typical 0.5-1.5. Steeper curves are for less-insulated buildings or radiator systems.

    • offset: Supply temperature in °C at outdoor temperature 0 °C.

    • min_supply: Minimum supply temperature in °C. Defaults to 25. Heat pump never goes below this.

    • max_supply: Maximum supply temperature in °C. Defaults to 70. Heat pump never goes above this.

    • Example for radiators in a Belgian terraced house: {"slope": 1.0, "offset": 35, "min_supply": 28, "max_supply": 55}

      • At -10 °C outdoor: supply = 45 °C

      • At 0 °C outdoor: supply = 35 °C

      • At 12 °C outdoor: supply = 23 °C, clipped to 28 °C floor

    • Example for underfloor: {"slope": 0.6, "offset": 30, "min_supply": 25, "max_supply": 40}

When heating_curve is configured, COP is computed per timestep with the per-timestep supply temperature, so the optimizer sees realistic COP variation across the day. This matters most for mild-weather operation where a fixed-55 °C supply T would underestimate HP COP by 25-40 %.

Domestic-hot-water tanks should not use a heating curve - DHW needs a fixed setpoint regardless of outdoor temperature. Configure them as a separate thermal_battery (or a separate source in the graph topology) with supply_temperature: 55 or similar.

Constant-efficiency mode (gas boiler, oil burner, district heating)#

The default thermal battery model uses a Carnot-based COP that varies with outdoor temperature - appropriate for heat pumps. Non-electric heat sources (gas boilers, oil burners, district heating) convert input power to heat at a roughly constant efficiency that does not depend on outdoor temperature. For these sources, set the efficiency parameter:

  • efficiency: Optional constant energy-conversion factor (output thermal kW / input kW). When set, EMHASS skips the Carnot COP calculation and uses this flat value for every timestep. supply_temperature and carnot_efficiency become optional in this mode.

    • Typical values:

      • Modern condensing gas boiler: 0.90-0.95

      • Standard gas boiler: 0.85-0.90

      • Oil burner: 0.80-0.90

      • District heating substation: 0.95-0.98

      • Direct electric heater: 1.0

    • Example: 0.9 for a condensing gas boiler

    • When both efficiency and heat-pump fields are present, efficiency takes precedence.

Configure one thermal_battery per source-target pair to model hybrid systems. For example, a gas boiler serving both a heating buffer and a DHW tank is two def_load_config entries (one per target), grouped via deferrable_load_groups with mutual_exclusion: true and max_power equal to the boiler’s modulating maximum if the two targets share the same physical actuator.

Heating demand calculation#

EMHASS needs to know how much heat your building requires. There are two methods to calculate this, and EMHASS automatically selects the appropriate method based on which parameters you provide.

Method 2: Heating Degree Days (simpler, less accurate)#

This method uses historical heating consumption data. It requires:

  • specific_heating_demand: Annual heating energy demand in kWh/(m²·year).

    • Get this from your energy bills or energy certificate

    • Typical values:

      • Passive house: <15

      • Modern low-energy: 15-50

      • Standard modern: 50-100

      • Older buildings: 100-200

    • Example: 65.0

  • area: Heated floor area in m².

    • Example: 100.0

Optional HDD parameters:

  • base_temperature: Base temperature for heating degree day calculation in °C (default: 18.0).

  • annual_reference_hdd: Annual heating degree days for your location (default: 3000.0).

    • Northern Europe: 3500-5000

    • Central Europe: 2500-3500

    • Southern Europe: 1500-2500

Physical constants#

By default, the thermal battery assumes concrete as the storage medium. You can override the physical constants to model other media such as water (for hot water tanks).

  • density: Density of the thermal storage medium in kg/m³ (default: 2400).

    • Concrete: 2400

    • Water: 997

    • Example: 997 for a hot water tank

  • heat_capacity: Specific heat capacity of the thermal storage medium in kJ/(kg·°C) (default: 0.88).

    • Concrete: 0.88

    • Water: 4.184

    • Example: 4.184 for a hot water tank

  • thermal_loss: Constant standby heat loss rate from storage to environment in kW (default: 0.045).

    • For underfloor heating in concrete slab: 0.045

    • For a well-insulated hot water tank: 0.02-0.04

    • Example: 0.035

All three values must be positive. Invalid values raise an error.

Hot water tank mode (draw-off demand)#

When draw_off_demand is present, the thermal battery switches to hot water tank mode. In this mode, the building heating demand calculation is skipped entirely. Instead, the tank has:

  • A constant standby loss (thermal_loss) — heat escaping the tank to the surrounding room.

  • A draw-off demand profile — energy withdrawn by hot water usage (showers, taps, etc.).

This is appropriate because a hot water tank sits in a room at roughly constant temperature — there are no outdoor-temperature-dependent losses, no solar gains, and no internal gains.

  • draw_off_demand: Daily profile of hot water draw-off energy in kWh per timestep (default: none).

    • A list of energy values representing one day of hot water consumption

    • The profile is automatically tiled (repeated) to fill the optimization horizon

    • Each value represents the energy withdrawn during that timestep

    • Example for 30-minute timesteps: [0,0,0,0,0,0, 0,0,0,0,0,0, 0.5,0.3,0,0,0,0, 0,0,0,0,0,0, 0,0,0,0,0,0, 0,0,0,0,0,0, 0.8,0.5,0.3,0,0,0, 0,0,0,0,0,0] (morning shower around 06:00, evening shower around 18:00)

When draw_off_demand is absent (or empty), the existing behavior applies — building heating demand with outdoor-temperature-dependent losses. This preserves backward compatibility for floor heating use cases.

The temperature dynamics in hot water tank mode:

conversion = 3600 / (density * heat_capacity * volume)

predicted_temp[t+1] = predicted_temp[t]
    + conversion * (cop[t] * p_deferrable[t] / 1000 * dt - draw_off_demand[t] - thermal_loss)

Weather-compensated minimum temperature (radiator emission floor)#

For radiator-based heating systems, the buffer / storage temperature must stay above a level where the radiator can still deliver the building’s heat demand. Radiator emission follows Q āˆ (T_water āˆ’ T_room)^1.3, so the floor depends on outdoor temperature: cold day → higher floor needed.

Set min_temperature_curve to make the floor track outdoor temperature via the same linear law as heating_curve:

  • min_temperature_curve: Dict describing the weather-compensated minimum: T_min = clip(offset - slope * T_outdoor, min_supply, max_supply). When present, the per-slot effective minimum is max(static_min_temperatures[t], curve_min[t]) so any static absolute floor still wins if it’s higher.

    • slope, offset: same form as the source’s heating curve.

    • min_supply: Absolute floor in °C, never below this regardless of mild weather. Choose this as the buffer T below which your radiators cannot deliver useful heat (typically 28-30 °C).

    • max_supply: Upper bound on the dynamic floor (not the tank max - that’s still max_temperatures).

    • Example: {"slope": 1.0, "offset": 35, "min_supply": 30, "max_supply": 55}

      • At 10 °C outdoor: floor = 30 (clipped)

      • At -5 °C outdoor: floor = 40

      • At -15 °C outdoor: floor = 50

The min_temperature_curve is independent of heating_curve on a source: the source curve sets supply T to the buffer, the storage curve sets the floor the buffer must respect. In a well-tuned system they’re related — the source curve typically matches or runs slightly above the storage floor curve so the source always has headroom to recharge the buffer.

For underfloor / slab systems the same idea applies but with a lower band (e.g., min_supply: 22, max_supply: 32).

Soft constraints (desired temperature / overshoot)#

By default, min_temperatures and max_temperatures are enforced as hard constraints — the optimizer must keep the storage temperature strictly within bounds. You can optionally add soft constraints using desired temperatures and overshoot detection, following the same pattern as thermal_config.

When configured, the optimizer penalizes deviations from the desired temperature and suppresses heating when the storage temperature overshoots:

  • desired_temperatures: Target temperatures in °C per timestep (default: none).

    • When present, enables soft comfort constraints

    • The penalty for deviating from these targets is added to the objective

    • Example: [50.0] * 48 for constant 50°C target in a hot water tank

  • overshoot_temperature: Temperature threshold above which heating is suppressed in °C (default: none).

    • When the predicted temperature exceeds this value, the heat pump is forced off

    • Prevents wasteful overheating

    • Example: 55.0

  • penalty_factor: Weight of the comfort deviation penalty in the objective (default: 10).

    • Higher values make the optimizer try harder to hit desired temperatures

    • Lower values give the optimizer more flexibility to shift heating for cost savings

    • Example: 10

  • sense: Direction of thermal control (default: "heat").

    • "heat": Penalizes temperatures below desired (standard heating)

    • "cool": Penalizes temperatures above desired (cooling mode)

    • Example: "heat"

Heat pump group coupling#

If a single heat pump serves multiple thermal loads (e.g., underfloor heating AND a hot water tank), declare them as a mutual-exclusion group via optim_conf.deferrable_load_groups. The optimizer then ensures at most one load is active per timestep — matching the real-world constraint where a valve switches the heat pump between circuits.

optim_conf:
  deferrable_load_groups:
    - names: ["deferrable0", "deferrable1"]
      mutual_exclusion: true

Members can be any mix of semi-continuous and non-semi-continuous loads. For semi-continuous members the optimizer reuses the on/off binary (p_def_bin2); for non-semi-continuous members an anonymous activity binary is created and linked to the power variable so the same sum(activity[k]) <= 1 constraint applies.

Advanced parameters#

  • thermal_loss: Base thermal loss coefficient from storage to environment in kW (default: 0.045).

    • Only adjust this if you have measured data showing different loss rates

    • Example: 0.045

Thermal inertia (optional)#

Real heating systems have a delay between the heat pump operating and the heat actually reaching the thermal mass (e.g., water circulating through underfloor pipes, slab warming up). The default model treats heat input as instantaneous, which can cause the optimizer to schedule heating at suboptimal times — especially for short pre-heating windows in MPC mode.

The thermal_inertia_time_constant parameter adds a first-order low-pass filter on the heat input, modeling this physical delay. When set, a new state variable Q_input tracks the effective heat energy reaching the thermal mass, smoothing out the raw heat pump output.

  • thermal_inertia_time_constant: Time constant (Ļ„) of the thermal inertia filter in hours (default: 0.0).

    • 0.0 (default): No filter, original instantaneous model — fully backward compatible

    • 0.5-1.0: Light filtering, suitable for well-coupled radiator systems

    • 1.0-3.0: Moderate filtering, typical for underfloor heating with concrete screed

    • 3.0-4.0: Heavy filtering, thick slabs or poorly coupled systems

    • Values above 6.0 trigger a warning (unusually large)

    • Negative values raise an error

    • Example: 2.0 for a typical underfloor heating system

The filter equation at each timestep is:

Q_input[t+1] = Q_input[t] + α Ɨ (raw_heat[t] - Q_input[t])

where α = time_step / Ļ„ (clamped to 1.0 if Ļ„ < time_step). The temperature equation then uses Q_input instead of the raw heat pump output.

Warm-starting Q_input in MPC mode#

When using MPC (repeated optimizations), Q_input automatically persists between solves via the optimization cache. The value from timestep 1 of the previous solve becomes the initial value for the next solve. This means the optimizer ā€œremembersā€ the thermal state of the system without any manual intervention.

For manual control, you can override the initial Q_input value:

  • q_input_initial: Manual override for the initial Q_input value in kWh (default: 0.0).

    • Only needed if you want to explicitly set the starting thermal energy in the filter

    • When set, it takes priority over the auto-persisted value from the previous solve

    • Example: 0.5

Published sensors#

When thermal_inertia_time_constant > 0, an additional sensor is published:

  • sensor.q_input_heater{k} — Filtered heat input reaching the thermal mass (kWh per timestep)

This sensor shows the effective heat delivery after accounting for the system’s thermal lag. Compare it with P_deferrable{k} to see the smoothing effect.

Example configurations#

Example 1: Modern home with underfloor heating, solar and internal gains#

This example shows a well-insulated modern home with underfloor heating, using the physics-based heating demand calculation including solar gains through windows and internal gains from electrical appliances.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 35.0,
        "volume": 18.0,
        "start_temperature": 22.0,
        "min_temperatures": [20.0] * 48,  # Constant 20°C minimum
        "max_temperatures": [28.0] * 48,  # Constant 28°C maximum
        "carnot_efficiency": 0.45,
        "u_value": 0.35,
        "envelope_area": 380.0,
        "ventilation_rate": 0.4,
        "heated_volume": 240.0,
        "window_area": 28.0,
        "shgc": 0.6,
        "internal_gains_factor": 0.7
      }
    }
  ]
}

This configuration:

  • Models a 90m² underfloor heating slab with 20cm screed (90 Ɨ 0.2 = 18 m³)

  • Uses 35°C supply temperature (typical for underfloor heating)

  • Efficient modern heat pump (45% Carnot efficiency)

  • Well-insulated building (U-value 0.35)

  • Includes solar gains through 28m² of south-facing windows

  • Accounts for 70% of electrical load becoming internal heat gains

  • Maintains floor temperature between 20-28°C

Example 2: Older home with radiators, simple configuration#

This example uses the simpler HDD-based approach for an older home with radiator heating.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 50.0,
        "volume": 12.0,
        "start_temperature": 45.0,
        "min_temperatures": [40.0] * 48,  # Constant 40°C minimum
        "max_temperatures": [65.0] * 48,  # Constant 65°C maximum
        "carnot_efficiency": 0.38,
        "specific_heating_demand": 95.0,
        "area": 120.0,
        "base_temperature": 18.0,
        "annual_reference_hdd": 2800.0
      }
    }
  ]
}

This configuration:

  • Models a 60m² concrete floor as thermal mass (60 Ɨ 0.2 = 12 m³)

  • Uses 50°C supply temperature (needed for radiators)

  • Standard efficiency heat pump (38% Carnot efficiency, lower due to higher supply temperature)

  • Older building consuming 95 kWh/m²/year

  • 120m² heated floor area

  • Maintains thermal mass between 40-65°C

Example 3: Underfloor heating with thermal inertia#

This example shows how to use the thermal inertia filter for a system where there is a measurable delay between heat pump operation and temperature change in the slab.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 35.0,
        "volume": 18.0,
        "start_temperature": 22.0,
        "min_temperatures": [20.0] * 48,
        "max_temperatures": [28.0] * 48,
        "carnot_efficiency": 0.45,
        "u_value": 0.35,
        "envelope_area": 380.0,
        "ventilation_rate": 0.4,
        "heated_volume": 240.0,
        "thermal_inertia_time_constant": 2.0
      }
    }
  ]
}

This configuration:

  • Uses a 2-hour thermal inertia time constant, modeling the delay in heat transfer through the concrete slab

  • The optimizer will schedule heating earlier to account for the lag, resulting in better pre-heating behavior

  • The q_input_heater0 sensor shows the filtered heat delivery to the slab

  • In MPC mode, Q_input automatically persists between solves for continuity

Example 4: Multiple deferrable loads#

If you have other deferrable loads (EV charger, dishwasher, etc.) along with your thermal battery:

{
  "def_load_config": [
    {},
    {
      "thermal_battery": {
        "supply_temperature": 35.0,
        "volume": 15.0,
        "start_temperature": 22.0,
        "min_temperatures": [20.0] * 48,  # Constant 20°C minimum
        "max_temperatures": [26.0] * 48,  # Constant 26°C maximum
        "u_value": 0.45,
        "envelope_area": 320.0,
        "ventilation_rate": 0.5,
        "heated_volume": 200.0
      }
    },
    {}
  ]
}

In this case:

  • Load 0: Regular deferrable load (e.g., EV charger)

  • Load 1: Thermal battery with heat pump

  • Load 2: Another regular deferrable load (e.g., washing machine)

Example 5: Hot water tank#

A 200-liter hot water tank heated by a heat pump, with a daily shower profile.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 45.0,
        "volume": 0.2,
        "density": 997,
        "heat_capacity": 4.184,
        "thermal_loss": 0.035,
        "start_temperature": 50.0,
        "min_temperatures": [40.0] * 48,
        "max_temperatures": [60.0] * 48,
        "carnot_efficiency": 0.40,
        "draw_off_demand": [0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.5,0.3,0,0,0,0, 0,0,0,0,0,0,
                            0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.8,0.5,0.3,0,0,0, 0,0,0,0,0,0]
      }
    }
  ]
}

This configuration:

  • Models a 200-liter (0.2 m³) hot water tank with water physics (density=997 kg/m³, heat_capacity=4.184 kJ/(kg·°C))

  • Uses 45°C supply temperature (typical for domestic hot water)

  • Has a constant 0.035 kW standby loss (well-insulated tank)

  • Defines a daily draw-off profile (48 half-hour timesteps): morning shower at 06:00 (0.5 + 0.3 kWh) and evening shower at 18:00 (0.8 + 0.5 + 0.3 kWh)

  • The profile repeats automatically if the optimization horizon exceeds 24 hours

  • Maintains tank temperature between 40-60°C

Example 6: Hot water tank#

A 200-liter hot water tank heated by a heat pump, without any draw_off_demand.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 45.0,
        "volume": 0.2,
        "density": 997,
        "heat_capacity": 4.184,
        "thermal_loss": 0.035,
        "start_temperature": 50.0,
        "min_temperatures": [40.0] * 48,
        "max_temperatures": [60.0] * 48,
        "carnot_efficiency": 0.40,
        "specific_heating_demand": 0.0,
        "area": 1.0
      }
    }
  ]
}

This configuration:

  • Models a 200-liter (0.2 m³) hot water tank with water physics (density=997 kg/m³, heat_capacity=4.184 kJ/(kg·°C))

  • Uses 45°C supply temperature (typical for domestic hot water)

  • Has a constant 0.035 kW standby loss (well-insulated tank)

  • This config does not define a demand profile. To ensure backward compatibility, the parameters specific_heating_demand and area must be present.

  • Maintains tank temperature between 40-60°C

Example 6b: Direct heating (no buffer tank)#

For installations where the heat source feeds radiators directly without an intermediate buffer (common in older homes and apartments), model the building itself as the storage. The building’s thermal mass (walls, screed, furniture, air) plays the role of the buffer; the optimizer tracks an effective indoor temperature.

Without a draw_off_demand, the thermal_battery automatically switches to space-heating mode and uses the building physics (u_value, envelope_area, ventilation_rate, heated_volume) to compute heat loss.

{
  "def_load_config": [
    {
      "thermal_battery": {
        # The building is the thermal mass. Sizing rules of thumb:
        # concrete equivalent ~ 0.05 m^3 per m^3 of heated volume
        # for a typical brick / concrete envelope (heavier construction -> more).
        "volume": 12.0,            # m^3 equivalent
        "density": 2400, "heat_capacity": 0.88,  # concrete defaults
        "thermal_loss": 0.05,
        "start_temperature": 20.0,      # current measured indoor T
        "min_temperatures": [19.0]*48,  # comfort lower bound
        "max_temperatures": [22.0]*48,  # comfort upper bound
        # Building envelope physics drives the demand each slot.
        "u_value": 0.45,
        "envelope_area": 180.0,
        "ventilation_rate": 0.4,
        "heated_volume": 240.0,
        "indoor_target_temperature": 21.0,
        # Source: constant-efficiency for gas, supply_temperature/heating_curve for HP
        "efficiency": 0.92
      }
    }
  ]
}

This configuration:

  • Treats the heated zone as one thermal node tracked between 19 and 22 °C

  • Computes building heat loss each slot via the existing physics-based method

  • Lets the optimizer shift gas/HP firing into the cheapest slot of the day while keeping the indoor temperature inside the comfort band

  • Reuses every existing capability: heating curve on the source, weather-compensated minimum temperature, soft comfort relaxation, mutex with DHW or other zones

The same pattern works in the graph topology API: declare one storage node representing the building (with the envelope params as a building_demand consumer attached) and the source flowing into it. No buffer required.

Example 7: Hot water tank with soft constraints#

Same hot water tank but with soft constraints to target 50°C while allowing deviations when electricity is expensive.

{
  "def_load_config": [
    {
      "thermal_battery": {
        "supply_temperature": 45.0,
        "volume": 0.2,
        "density": 997,
        "heat_capacity": 4.184,
        "thermal_loss": 0.035,
        "start_temperature": 50.0,
        "min_temperatures": [40.0] * 48,
        "max_temperatures": [60.0] * 48,
        "desired_temperatures": [50.0] * 48,
        "overshoot_temperature": 55.0,
        "penalty_factor": 10,
        "sense": "heat",
        "carnot_efficiency": 0.40,
        "draw_off_demand": [0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.5,0.3,0,0,0,0, 0,0,0,0,0,0,
                            0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.8,0.5,0.3,0,0,0, 0,0,0,0,0,0]
      }
    }
  ]
}

This configuration:

  • Targets 50°C (desired) but allows the optimizer to let it drop toward 40°C (min) when electricity is expensive

  • Suppresses heating when temperature exceeds 55°C (overshoot)

  • The penalty factor (10) balances comfort vs cost — increase for tighter temperature control

Example 8: Heat pump group (underfloor heating + hot water tank)#

A single heat pump serving both underfloor heating and a hot water tank. The optimizer ensures only one is active at a time.

{
  "num_def_loads": 2,
  "nominal_power_of_deferrable_loads": [1000, 2000],
  "treat_deferrable_load_as_semi_cont": [true, false],
  "def_load_config": [
    {
      "thermal_battery": {
        "indoor_target_temperature": 22,
        "volume": 8,
        "u_value": 0.3,
        "envelope_area": 400.0,
        "ventilation_rate": 0.5,
        "heated_volume": 450.0,
        "carnot_efficiency": 0.32,
        "supply_temperature": 30.0,
        "min_temperatures": [20.0] * 48,
        "max_temperatures": [22.0] * 48,
        "start_temperature": 20.0
      }
    },
    {
      "thermal_battery": {
        "supply_temperature": 45.0,
        "volume": 0.2,
        "density": 997,
        "heat_capacity": 4.184,
        "thermal_loss": 0.035,
        "carnot_efficiency": 0.32,
        "start_temperature": 50.0,
        "min_temperatures": [40.0] * 48,
        "max_temperatures": [60.0] * 48,
        "carnot_efficiency": 0.40,
        "draw_off_demand": [0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.5,0.3,0,0,0,0, 0,0,0,0,0,0,
                            0,0,0,0,0,0, 0,0,0,0,0,0,
                            0.8,0.5,0.3,0,0,0, 0,0,0,0,0,0]
      }
    }
  ]
}

This configuration:

  • Load 0: Underfloor heating (semi-continuous, modulates 0-1000W) using thermal_battery

  • Load 1: Hot water tank (non-semi-continuous, fixed 2000W) using thermal_battery

Couple them by adding a mutual-exclusion entry to optim_conf:

optim_conf:
  deferrable_load_groups:
    - names: ["deferrable0", "deferrable1"]
      mutual_exclusion: true

The optimizer reuses the on/off binary for the semi-continuous load and creates an anonymous activity binary for the hot water tank, then enforces sum(activity[k]) <= 1 at every timestep.

How the optimization works#

The thermal battery optimization uses a physics-based model with three main components:

1. Heat pump COP (Coefficient of Performance)#

The heat pump COP varies with outdoor temperature. EMHASS calculates this using a Carnot-based formula:

COP = carnot_efficiency Ɨ T_supply_K / (T_supply_K - T_outdoor_K)

Where temperatures are in Kelvin (K = °C + 273.15).

Example: With 35°C supply, 5°C outdoor, and 0.4 Carnot efficiency:

  • COP = 0.4 Ɨ 308.15 / 30 = 4.1

  • Meaning: for every 1 kWh of electricity, you get 4.1 kWh of heat

Key insights:

  • COP is higher when outdoor temperature is closer to supply temperature

  • Lower supply temperatures (underfloor heating) give better COP than high temperatures (radiators)

  • The carnot_efficiency parameter lets you match your specific heat pump’s performance

2. Thermal losses#

The thermal storage gradually loses heat to the environment. The loss model depends on the mode:

Building heating mode (no draw_off_demand): Uses the methodology from Langer & Volling (2020):

Loss = thermal_loss Ɨ (1 - 2 Ɨ Hot)

Where Hot = 1 if outdoor temp ≄ indoor temp, else 0. This means losses are positive when it’s cold outside (heat escapes) and negative when warm (passive heat gain).

Hot water tank mode (with draw_off_demand): Uses a constant standby loss:

Loss = thermal_loss  (constant, not dependent on outdoor temperature)

This is appropriate because a tank sits indoors at roughly constant ambient temperature.

3. Heating demand / draw-off demand#

Building heating mode: The building requires heat to maintain comfort. Calculated from:

  • Physics-based: transmission losses + ventilation losses - solar gains

  • HDD-based: historical consumption scaled by current weather

Hot water tank mode: The draw-off demand profile replaces the building heating demand. It represents energy withdrawn by hot water consumption (showers, taps). The daily profile is tiled to fill the optimization horizon.

4. Thermal balance#

At each timestep, the storage temperature changes based on:

conversion = 3600 / (density Ɨ heat_capacity Ɨ volume)

predicted_temp[t+1] = predicted_temp[t]
    + conversion Ɨ (cop[t] Ɨ P[t] / 1000 Ɨ dt - demand[t] - loss[t])

Where demand[t] is either building heating demand or draw-off demand, and loss[t] is either outdoor-temperature-dependent or constant, depending on the mode.

The optimizer decides when to run the heat pump to:

  • Minimize electricity costs (plus comfort penalty if soft constraints are configured)

  • Keep storage temperature within min/max bounds (hard constraints)

  • Approach desired temperatures if configured (soft constraints)

  • Respect mutual exclusivity if listed in a deferrable_load_groups entry with mutual_exclusion: true

5. Mutual exclusion via deferrable_load_groups (optional)#

When multiple deferrable loads are listed in a deferrable_load_groups entry with mutual_exclusion: true, the optimizer adds:

sum(activity_binary[k][t] for k in group) <= 1,  for all t

This ensures at most one load is active per timestep. Both loads can be off simultaneously. The optimizer decides the optimal time allocation between members to minimize total cost while satisfying all temperature constraints. Members may be a mix of semi-continuous and non-semi-continuous loads.

6. Thermal inertia filter (optional)#

When thermal_inertia_time_constant is set to a value greater than 0, the raw heat pump output passes through a first-order low-pass filter before affecting the storage temperature. This models the physical delay in heat transfer (e.g., water circulating through pipes, concrete warming up).

The filter introduces a new state variable Q_input that tracks the effective heat delivery:

Q_input[t+1] = Q_input[t] + (Ī”t/Ļ„) Ɨ (raw_heat[t] - Q_input[t])

The temperature equation then uses Q_input instead of the raw heat, resulting in a smoother, delayed temperature response that better matches real-world behavior. This is particularly beneficial for MPC mode where short prediction horizons can lead to suboptimal scheduling without accounting for the thermal lag.

Calibrating your thermal battery parameters#

Step 1: Measure your building#

For physics-based approach:

  1. U-value: Check your energy performance certificate, or use typical values based on your building age

  2. Envelope area: Measure or calculate from building plans (walls + roof + floor)

  3. Ventilation rate: Check your ventilation system specs, or use 0.4-0.5 for typical homes

  4. Heated volume: Floor area Ɨ ceiling height

For HDD approach:

  1. Specific heating demand: Check energy bills (annual heating kWh / floor area m²)

  2. Area: Measure your heated floor area

Step 2: Determine thermal mass volume#

For underfloor heating:

  • Measure floor area that has heating pipes

  • Measure screed thickness (typically 15-25 cm)

  • Volume = area Ɨ thickness (in meters)

  • Example: 75 m² floor with 20 cm screed = 75 Ɨ 0.2 = 15 m³

For radiator systems with thermal mass:

  • Estimate the concrete/masonry volume that stores heat

  • Include floor slabs, internal walls in heated areas

  • Be conservative (underestimate rather than overestimate)

Step 3: Find your heat pump supply temperature#

Check your heat pump controller or settings:

  • For underfloor: usually shown as ā€œflow temperatureā€ or ā€œsupply tempā€

  • Typical range: 30-40°C depending on outdoor temp (heat curve)

  • For the optimizer, use a typical mid-season value (e.g., 35°C)

Step 4: Calibrate Carnot efficiency#

Method 1 - From manufacturer specs:

  • Find your heat pump’s rated COP at a specific test condition (e.g., A7/W35)

  • A7/W35 means: 7°C outdoor air, 35°C water output

  • Calculate: carnot_eff = COP_rated Ɨ (T_supply_K - T_outdoor_K) / T_supply_K

  • Example: COP = 4.5 at A7/W35

    • Ī”T = 35 - 7 = 28 K

    • carnot_eff = 4.5 Ɨ 28 / 308.15 = 0.409 ā‰ˆ 0.41

Method 2 - From real data:

  • Monitor your heat pump for a few days

  • Record: electricity consumed, heat delivered (if your heat pump shows this), outdoor temp, supply temp

  • Calculate: actual COP = heat delivered / electricity consumed

  • Then: carnot_eff = COP_actual Ɨ (T_supply_K - T_outdoor_K) / T_supply_K

Typical values:

  • Modern inverter heat pump: 0.40-0.50

  • Standard on/off heat pump: 0.35-0.42

  • Older heat pump: 0.30-0.38

Step 5: Validate and tune#

Run the optimization for a past week and compare:

  • Predicted vs actual heat pump runtime

  • Predicted vs actual energy consumption

  • Predicted vs actual floor/storage temperatures

If there’s more than 20% difference:

  • Adjust U-value if heating demand is consistently wrong

  • Adjust carnot_efficiency if COP seems wrong

  • Adjust thermal mass volume if temperature changes are too fast/slow

Runtime parameters for optimization#

When calling the optimization API (day-ahead or MPC), you need to provide the thermal battery configuration. Here’s a complete example:

rest_command:
  emhass_thermal_battery_optim:
    url: http://localhost:5000/action/naive-mpc-optim
    method: post
    headers:
      content-type: application/json
    payload: >
      {
        "prediction_horizon": 24,
        "load_cost_forecast": {{ (state_attr('sensor.electricity_price', 'forecasts') | map(attribute='price') | list)[:24] | tojson }},
        "outdoor_temperature_forecast": {{ (state_attr('sensor.weather_forecast', 'forecast') | map(attribute='temperature') | list)[:24] | tojson }},
        "def_load_config": [
          {
            "thermal_battery": {
              "supply_temperature": 35.0,
              "volume": 18.0,
              "start_temperature": {{ states('sensor.floor_temperature') | float }},
              "min_temperatures": {{ [20.0] * 24 | tojson }},
              "max_temperatures": {{ [28.0] * 24 | tojson }},
              "carnot_efficiency": 0.42,
              "u_value": 0.35,
              "envelope_area": 380.0,
              "ventilation_rate": 0.4,
              "heated_volume": 240.0,
              "window_area": 28.0,
              "shgc": 0.6
            }
          }
        ]
      }

Important notes:

  • outdoor_temperature_forecast is required for thermal battery optimization (building heating mode)

  • start_temperature should ideally come from a real sensor (floor temp for underfloor heating, tank sensor for hot water)

  • If using solar gains, ensure your forecast data includes ghi (global horizontal irradiance)

  • Add "thermal_inertia_time_constant": 2.0 to the thermal_battery dict to enable the thermal inertia filter

  • In MPC mode, Q_input auto-persists between solves; use "q_input_initial": 0.5 to manually override

  • For hot water tanks, add "density": 997, "heat_capacity": 4.184 and a "draw_off_demand" profile or "specific_heating_demand": 0.0, "area":1.0

  • For heat pump groups, list both deferrable indices in optim_conf.deferrable_load_groups with mutual_exclusion: true

Published sensors#

After running optimization and publishing results, EMHASS creates these sensors in Home Assistant:

For each thermal battery (where k is the load index, starting from 0):

  1. sensor.p_deferrable{k} - Heat pump power schedule (W)

  2. sensor.heating_demand{k} - Heating energy demand per timestep (kWh)

  3. sensor.temp_predicted{k} - Predicted thermal storage temperature (°C)

  4. sensor.q_input_heater{k} - Filtered heat input (kWh per timestep) — only when thermal_inertia_time_constant > 0

You can customize these sensor names:

{
  "custom_deferrable_forecast_id": [
    {
      "entity_id": "sensor.heatpump_power_schedule",
      "friendly_name": "Heat Pump Power Schedule"
    }
  ],
  "custom_heating_demand_id": [
    {
      "entity_id": "sensor.heating_demand",
      "friendly_name": "Heating Demand"
    }
  ],
  "custom_predicted_temperature_id": [
    {
      "entity_id": "sensor.floor_temperature_predicted",
      "friendly_name": "Floor Temperature (Predicted)"
    }
  ]
}

Using the optimization results#

Controlling your heat pump#

Create an automation that follows the optimized schedule:

automation:
  - alias: "Heat Pump - EMHASS Optimal Control"
    trigger:
      - platform: state
        entity_id: sensor.heatpump_power_schedule
    action:
      - choose:
          - conditions:
              - condition: template
                value_template: "{{ states('sensor.heatpump_power_schedule') | float > 100 }}"
            sequence:
              - service: climate.turn_on
                target:
                  entity_id: climate.heat_pump
          - conditions:
              - condition: template
                value_template: "{{ states('sensor.heatpump_power_schedule') | float <= 100 }}"
            sequence:
              - service: climate.turn_off
                target:
                  entity_id: climate.heat_pump

Monitoring heating costs#

Track your heating expenses:

template:
  - sensor:
      - name: "Heating Cost Today"
        unit_of_measurement: "€"
        device_class: monetary
        state: >
          {% set demand = states('sensor.heating_demand') | float %}
          {% set price = states('sensor.electricity_price') | float %}
          {{ (demand * price) | round(2) }}

Energy dashboard integration#

Add the heating demand sensor to Home Assistant’s energy dashboard to track heating energy consumption over time.

Troubleshooting#

Optimization returns ā€œInfeasibleā€#

Possible causes:

  • Temperature constraints too tight (try widening min/max range)

  • Thermal mass volume too small for the heating demand

  • Heat pump power rating too low

  • Heat pump group: loads in the same group compete for time — not enough timesteps to satisfy both

Solutions:

  • Increase the gap between min and max temperatures

  • Verify your volume calculation is correct

  • Check that nominal_power_of_deferrable_loads is set correctly for your heat pump

  • For heat pump groups: widen temperature bounds on one or both loads, or increase the prediction horizon

COP values seem wrong#

Check these:

  • Supply temperature is correct for your system (30-40°C underfloor, 50-70°C radiators)

  • Outdoor temperature forecast is in Celsius (not Fahrenheit!)

  • Carnot efficiency is reasonable (0.35-0.50)

Expected COP ranges:

  • Underfloor (35°C) at 5°C outdoor: COP ā‰ˆ 4.1

  • Radiators (50°C) at 5°C outdoor: COP ā‰ˆ 2.9

  • Very cold weather (35°C, -10°C): COP ā‰ˆ 2.7

Heating demand too high or too low#

For physics-based method:

  • Check U-value is realistic for your building

  • Verify envelope area includes all exterior surfaces

  • Ensure ventilation rate matches your actual system

For HDD method:

  • Verify specific_heating_demand matches your energy bills

  • Check that area is heated floor area (not total building area)

Floor gets too hot or too cold#

The optimizer is keeping storage temperature within bounds, but:

  • If too hot: lower the values in max_temperatures

  • If too cold: raise the values in min_temperatures

  • If temperature swings are too large: check your thermal mass volume is accurate

  • Consider using variable temperature limits (night setback) by adjusting the list values

Thermal inertia not having an effect#

If you set thermal_inertia_time_constant but don’t see a difference:

  • Check the value is greater than 0 (Ļ„=0 disables the filter)

  • The effect is most visible in MPC with short prediction horizons

  • Compare q_input_heater0 with P_deferrable0 — if they look identical, Ļ„ may be too small relative to your time step

  • If Ļ„ < time_step (e.g., Ļ„=0.3h with 30min steps), the filter coefficient is clamped to 1.0, effectively bypassing the filter

Solar gains not working#

Requirements for solar gains:

  1. Define window_area in your config

  2. Optimization data must include ghi (global horizontal irradiance) column

  3. Must use physics-based method (not HDD method)

Check the logs for: ā€œUsing physics-based heating demand with solar gainsā€

Hot water tank temperature drops too fast#

If the tank temperature drops faster than expected:

  • Check thermal_loss is realistic for your tank insulation (typical: 0.02-0.04 kW)

  • Verify draw_off_demand values are in kWh per timestep (not total daily)

  • Check density (997 for water) and heat_capacity (4.184 for water) are correct

  • Verify volume matches your actual tank size in m³ (200 liters = 0.2 m³)

Heat pump group not enforcing mutual exclusivity#

If both loads in a group seem to run simultaneously:

  • Verify the loads are listed under the same deferrable_load_groups entry with mutual_exclusion: true

  • Check the indices in names (e.g., "deferrable0", "deferrable1") match your def_load_config order

  • A group with only one member silently has no effect; ensure both indices are listed

Soft constraints not working#

If desired_temperatures doesn’t seem to affect the optimization:

  • Ensure desired_temperatures is set (not just min_temperatures/max_temperatures)

  • Try increasing penalty_factor (higher = tighter tracking)

  • Check sense is correct: "heat" for heating, "cool" for cooling

  • If overshoot_temperature is too close to max_temperatures, the optimizer may have no room to maneuver

Tips for best results#

  1. Start simple: Use the HDD method first to get familiar, then switch to physics-based for better accuracy

  2. Measure accurately: The quality of your optimization depends on accurate parameters

  3. Monitor and adjust: Run the optimizer for a week, compare actual vs predicted, then tune parameters

  4. Give the optimizer flexibility: Use a reasonable temperature range (e.g., 20-28°C for underfloor) rather than a tight range (23-24°C). This allows the optimizer to find the most cost-effective solution.

  5. Update start temperature: For MPC, always use the actual current temperature from a sensor

  6. Consider weather: The optimizer works best when outdoor temperature forecasts are accurate

  7. Size your thermal mass correctly: For underfloor heating, measure the actual screed volume with heating pipes. Don’t include areas without heating.

  8. Model DHW explicitly: If your heat pump provides domestic hot water, model the tank as a separate thermal_battery with water physics (density: 997, heat_capacity: 4.184) and a draw_off_demand profile. Couple it with the space-heating load via optim_conf.deferrable_load_groups with mutual_exclusion: true.

  9. Solar gains matter: If you have significant south-facing windows, modeling solar gains can improve optimization accuracy by 10-20%

  10. Validate regularly: Compare predicted vs actual energy consumption weekly and adjust if needed

  11. Use thermal inertia for underfloor heating: If you notice the optimizer schedules heating too late for short pre-heating windows, try setting thermal_inertia_time_constant to 1.0-3.0 hours. This models the delay between heat pump operation and measurable temperature change in the slab.

References#